MGE Galaxy 3500 MGE Galaxy 3500 30kVA 400V 3:1 with 4 Battery Modules, Start-up 5X8 APC MGE Galaxy 3500, 24 kW / 30 kVA, Input 400V 3PH / Output 230V , Interface Port DB-9 RS-232 , Extended runtime model Includes Battery modules ship installed, Bolt down brackets, CD with software, Installation guide, Network Management Card, Power modules ship installed, Smart UPS signalling RS-232 cable, Start-Up Service, User Manual Output Output Power Capacity 24 kW / 30 kVA Max Configurable Power 24 kW / 30 kVA Nominal Output Voltage 230V Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage Efficiency at Full Load 96% Output Voltage Distortion Less than 5% Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal Crest Factor Unlimited Waveform Type Sine wave Output Connections (1) Hard Wire 5-wire (3PH + N + G) (1) Screw Terminals Output Voltage Tolerance +/-1% static and +/- 5% at 100% load step Output Voltage THD < 2% for 0 to 100% linear load and < 5% for full n Overload Operation 10 minutes @ 125% and 60 seconds @ 150% Efficiency at Half Load 95% Required Output Current Protection 50A Bypass Built-in Maintenance Bypass,Built-in Static Bypass Input Nominal Input Voltage 400V 3PH Input Frequency 40 - 70 Hz (auto sensing) Input Connections Hard Wire 5-wire (3PH + N + G) Input voltage range for main operations 304 - 477V Input voltage adjustable range for mains operation 340 - 460 (400V)V Other Input Voltages 380,415 Maximum Input Current 41A Input Breaker Capacity 50.0 A Input Total Harmonic Distortion Less than 5% for full load Type of Input Protection Required 3-pole breaker Batteries & Runtime Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof Included Battery Modules 4 Typical recharge time 5 hour(s) Nominal Battery Voltage +/-192 V (split battery referenced to neutral) End of Discharge Battery Voltage +/-154 V Efficiency in Battery Operation 95% Overload Operation 10 minutes @ 125% and 60 seconds @ 150% Communications & Management Interface Port(s) DB-9 RS-232 Pre-Installed SmartSlot™ Cards AP9631 Control panel Multi-function LCD status and control console Audible Alarm Alarm when on battery : distinctive low battery alarm : configurable delays Emergency Power Off (EPO) Yes Physical Maximum Height 1491.00 mm Maximum Width 523.00 mm Maximum Depth 838.00 mm Net Weight 656.00 KG Shipping Weight 686.00 KG Shipping Height 1643.00 mm Shipping Width 650.00 mm Shipping Depth 1062.00 mm Environmental Operating Environment 0 - 40 °C Operating Relative Humidity 0 - 95% Operating Elevation 0-999.9 meters Storage Temperature -15 - 45 °C Storage Relative Humidity 0 - 95% Storage Elevation 0-15000 meters Audible noise at 1 meter from surface of unit 55.00 dBA Online Thermal Dissipation 3931.00 BTU/hr Protection Class IP 51 Conformance Regulatory Approvals CE,EN 50091-2,EN/IEC 62040-3,EN/IEC 62040-1-1,IEC 61000-3-2,IEC 61000-3-3,ISO 14001,ISO 9001,VFI-SS-111 Standard Warranty 1 year repair or replace Features & Benefits Availability Increases availability by allowing the UPS to be connected to two separate power sources. Ensures clean, uninterrupted power to protected equipment while batteries are being replaced Increases total power capacity by using multiple UPSs simultaneously. Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high efficiency Gives higher application availability by correcting poor frequency and voltage conditions without using the battery. Supplies utility power to the connected loads in the event of a UPS overload condition or fault. Ensures clean, uninterrupted power to protected equipment when generator power is used. Serviceability Simplifies installation and maintenance while minimizing space requirements. Enables quick and simple replacement of air filters. Allows quick, easy battery replacement. With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you. Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it. Manageability Full-featured management via a Web browser as well as comprehensive management from a Network Management System. Prevent equipment failure from a full range of threatening environmental conditions. Text and mimic diagrams that display modes of operation, system parameters and alarms. Provides notification of changing utility power and UPS conditions Total Cost of Ownership Minimizes installation costs by enabling the use of smaller generators and cabling. Small UPS footprint provides maximum usage of valuable electrical room floorspace Prolongs battery life by regulating the charge voltage according to battery temperature.